160V Ratio Tester - Four-Level Undertaking Equipment Qualification Product Features:

1. The fully automatic transformer ratio and group tester has a wide test range, up to 10000.

2. Fast test speed, completes three-phase test in 7 seconds.

3. Z-connection transformer testing.

4. Has blind test ratio and group test functions. (When blind testing, the high-voltage side connection method must be known)

5. Non-volatile clock and date display, data storage function.

6. Protection function for reverse connection of high and low voltage.

7. Protection function for transformer short circuit and inter-turn short circuit.

8. Thermal printer output function, fast and silent.

9. Small size, light weight.

160V Ratio Tester - Four-Level Undertaking Equipment Qualification Functions



Fully Automatic Transformer Ratio and Group Tester The main function and purpose is to test the turns ratio or voltage ratio of power transformers during the production process of semi-finished and finished products, before new transformers are put into operation, and during the operation of transformers in the power system, according to the preventive test regulations of the Ministry of Power, which require regular turns ratio or voltage ratio tests on operating transformers. Traditional ratio bridges are cumbersome to operate, have non-intuitive readings, and require necessary conversions, with test results only providing data for one phase ratio. The fully automatic transformer ratio and group tester overcomes the shortcomings of traditional ratio bridge testing. The screen completes three-phase ratio testing in one go, with fast test speed and high accuracy. This greatly saves on-site testing time and brings high efficiency to customer tests.



Precautions:

1. Before using this instrument, be sure to read this operation manual carefully.

2. The operator of the instrument should have general knowledge of electrical equipment or instruments.

3. This instrument can be used indoors and outdoors, but should avoid use in places with rain, corrosive gases, excessive dust, high temperature, and direct sunlight.

4. The instrument should avoid severe vibration.

5. Maintenance, care, and adjustment of the instrument should be carried out by professionals.

6. The yellow, green, and red test clips correspond to phases A, B, and C of the transformer, respectively, and should not be connected incorrectly.

7. Do not reverse the high and low voltage cables.

8. When testing single-phase transformers, only use the yellow and green clips, do not use them incorrectly, and unused test clips should be left hanging.



Technical Parameters:

1. Range: 0.9 to 10000

2. Accuracy: 0.1%   digit (below 500)

       0.2% 2 digits (500 to 2000)

       0.3% digit (2000 to 4000)

       0.5% digit (above 4000)

3. Resolution: minimum 0.0001

4. Output voltage: 160V, 10V automatic gear shifting

5. Working power supply: AC220V   50HZ

6. Operating temperature: –20℃ to 40℃

7. Relative humidity: ≤85%, no condensation