Product Features of Series Resonance Test Device
1. Reactors of the same voltage level and capacity are smaller in size and lighter in weight; under rated load, temperature rise is minimal; using dry-type epoxy casting, mechanical strength
is high, electrical insulation performance is good, aesthetically pleasing and reliable
2. The variable frequency power supply control box has large capacity margin; strong protection functions; good output waveform; good stability; multiple working modes, easy operation; single-phase
220V or three-phase 380V input power supply universal, convenient for on-site power access
3. Flexible configuration. Different types of reactors can be selected to meet different test object requirements, achieving multi-purpose use of one machine with high cost performance
Technical Specifications:
| Rated Output Voltage | 0~1000kV and below |
| Output Frequency | 30~300Hz |
| Resonant Voltage Waveform | Pure sine wave, waveform distortion rate ≤1.0% |
| Duty Cycle | Continuous operation at full power for 60 minutes |
| Quality Factor | 30~90 |
| Frequency Adjustment Sensitivity | 0.1Hz |
| Instability | <0.05% |
| Working Power Supply | Single-phase 220V or three-phase 380V±10% |
| Power frequency 50Hz±5% |
Series Product Configurations and Applicable Scope:
| Product Model and Name | Applicable Scope (AC withstand voltage equipment for electrical equipment in substations of 10kV~500kV voltage levels, frequency 30~300Hz) | ||||
| Variable Frequency Source | Resonant Reactor | Excitation Transformer | Voltage Divider | Applicable Scope | |
| BPXZ-50/50/25 | 3kW | 25kV/1A two units (dry-type) |
3kVA (dry-type) |
50kV | 10kV power transformers up to 1000kVA and below 10kV switches, busbars, PT, CT, etc. 10kV (300mm2) cables ≤1.0km |
| BPXZ-108/108/27 | 5kW | 27kV/1A four units (dry-type) |
5kVA (dry-type) |
110kV | 35kV power transformers up to 31500kVA and below 35kV switches, busbars, PT, CT, etc. 10kV (300mm2) cables 2km 35kV (300mm2) cables 0.5km |
| BPXZ-200/200/50 | 10kW | 50kV/1A four units (dry-type) |
10kVA (dry-type) |
200kV | 110kV power transformers up to 50000kVA and below 110kV GIS, PT, CT, etc. (preventive tests) 35kV (300mm2) cables ≤1.0km 10kV (300mm2) cables ≤2.0km |
| BPXZ-270/270/45 | 15kW | 45kV/1A six units (dry-type) |
15kVA (dry-type) |
300kV | 110kV power transformers up to 50000kVA and below 110kV GIS, PT, CT, etc. 35kV (300mm2) cables ≤1.2km 10kV (300mm2) cables ≤3.0km |
| BPXZ-800/400/50 | 30kW | 50kV/2A eight units (dry-type) 100kV/2A four units (oil-immersed) |
30kVA (dry-type) 30kA (oil-immersed) |
400kV | 220kV power transformers up to 80000kVA and below 110kV power transformers up to 50000kVA and below 110kV/220kV GIS, PT, CT, etc. 35kV (300mm2) cables ≤2.0km 110kV (300mm2) cables ≤0.7km |
| BPXZ-1600/800/200 | 60kW | 200kV/2A four units (oil-immersed) |
60kVA (dry-type) |
800kV | 220kV power transformers up to 80000kVA and below 110kV power transformers up to 50000kVA and below 500kV GIS, PT, CT, etc. 220kV switches, GIS, PT, CT, etc. 110kV (400mm2) cables ≤1.5km 220kV (400mm2) cables ≤1.0km |
Note: Customized solutions can be provided based on the parameters of the test object.
Transformers, GIS systems, SF6 switches, CT/PT, insulators, busbars, cables, bushings and other capacitive equipment are the most common primary electrical equipment in substations. According to the test regulations for withstand voltage of primary electrical equipment in substations of 220V and below, the corresponding AC/DC withstand voltage test equipment must not only meet the test conditions of high voltage and low current, but also meet the test conditions of low voltage and high current, requiring a wide range of applicability. Using the principle of series resonance, the main equipment is composed of a variable frequency power supply control box (operation console), excitation transformer, reactor, and capacitive voltage divider. By connecting a rectifier stack and microammeter to the capacitive voltage divider, DC withstand voltage tests can be completed. Due to the excellent filtering characteristics after system resonance, the DC voltage produced is superior to that of ordinary test transformers after rectification. It is an ideal withstand voltage equipment for municipal, prefectural, and county-level high-voltage test departments and power installation, repair, and test engineering units.
◆ Reference schemes for selecting resonance test devices:
A. Reference scheme for cable resonance test device selection
B. Reference scheme for generator resonance test device selection
C. Reference scheme for substation electrical equipment resonance device selection
D. Reference scheme for CVT calibration resonance boost device selection
Variable frequency resonance product aliases
AC withstand voltage resonance device, variable frequency series resonance, series resonance, series resonance transformer, series resonance test equipment