Working Principle of Transformer Ratio Bridge Tester Technical Specifications
1. Ratio measurement range: 1~10000
2. Group: 1~12 points
3. Accuracy: 1~1000 0.2 class;
1000~10000 0.5 class
4. Power supply: AC220V ±10%, 50Hz
5. Operating ambient temperature: -5℃~40℃
6. Operating ambient humidity: <85%
7. Dimensions: 430×320×215 mm3
8. Weight: 5kg
Working Principle of Transformer Ratio Bridge Tester Usage Precautions:
1. During measurement, do not touch the test object.
2. If the test leads are short-circuited or the high and low voltage connections are reversed, the fuse will blow. After the fuse blows, if you proceed with measurement, the display will stop after showing "Measuring, please wait!". Please power off, replace the fuse with one of the same capacity, and retest.
3. Ensure good contact in connections, and the instrument should be properly grounded!
4. The working place of the instrument should be away from strong electric fields, strong magnetic fields, and high-frequency equipment. The less interference in the power supply, the better. It is advisable to use lighting circuits. If power supply interference is still significant, an AC purified power supply can be used to power the instrument, with a capacity greater than 200VA.
5. During operation, if the LCD display is disordered, all keys are unresponsive, or the measured values differ greatly from actual values, press the reset button or power off and restart the operation.
6. If the display shows no characters or the color is too faint, adjust the brightness potentiometer to a suitable position.
7. The instrument should be stored in a dry and ventilated place.
Technical Performance
1. Can measure various groups 0-11 (including Z connection) transformers, controlled by internal software, with simple external operation.
2. The fully automatic ratio tester has tap testing function, convenient for application.
3. High and low voltage isolation, can measure autotransformers.
4. Has the function of analyzing unknown groups and ratios.
5. Complete automatic protection system to avoid instrument damage.
6. Can automatically record data, and data is not lost after power off.