Transformer Tester / Inductance Tester Parameters Automatic Capacitance Bridge / Inductance Tester Parameters



Product Application:



It is specially developed under the guidance of the expert working group of reactive power compensation devices, aiming at the problems existing in on-site measurement of individual capacitor capacitance in shunt capacitor banks at substations. It mainly solves the following problems:



(1) On-site measurement of individual capacitors requires disconnecting connecting wires, which is not only heavy workload but also easy to damage capacitors;



(2) The low output voltage of capacitance meter leads to low fault detection rate.



(3) Measuring the inductance of reactors. This instrument has the advantages of small measurement workload, quick and simple operation, stable performance, accurate measurement, and high fault detection rate.



In addition, its current measurement unit can also be used for measuring electrical equipment such as CVT, lightning arrester, etc., with the function of one machine with multiple uses.



Technical Parameters:



1. Capacitance range: 0.2μF~2,000μF;



Capacity range: 5~20,000 kvar;



Measurement accuracy: ±1.5%×reading ±2 digits;



Resolution: ±1.0%rdg;



2. Inductance range: 1mH~9.99H; Measurement accuracy: ±1.5%±2 digits



3. Output measurement voltage: AC 26V/500VA; 50Hz;



4. Display mode: large screen LCD with full Chinese output, TPμp-40 panel thermal printer



5. Dimensions and weight: 370×370×220 mm / 8 kg



6. Working conditions:



Ambient temperature: 0℃ ~ +40℃, relative humidity: ≤90%



Power supply: AC 220V±10%; 50Hz;



Measurement range, resolution and error values































Capacitance measurement range:



Error value:



0.020μF ~ 0.200μF



±0.5%



0.200μF ~ 2.000μF



±0.5%



2.000μF ~ 20.00μF



±0.5%



20.00μF ~ 200.0μF



±0.5%



200.0μF ~ 2000.μF



±0.5%
































Capacitor reactive power



0 ~ 20.00Mvar



Error value



±1%



Capacitor active power



0 ~ 20.00kW



Error value



±1%



Capacitor dissipation factor



0 ~ 20.00%



Error value



±1%



Capacitor resistance component



0 ~ 10.00MΩ



Error value



±1%




























Inductance measurement range



Error value



0.10mH ~ 0.200H



±0.5%



2.000H ~ 20.00H



±0.5%



20.00H ~ 200.0H



±0.5%



200.0H ~ 2000.H



±0.5%
































Inductor reactive power



0 ~ 20.00Mvar



Error value



±1%



Inductor active power



0 ~ 20.00kW



Error value



±1%



Inductor dissipation factor



0 ~ 20.00%



Error value



±1%



Inductor resistance component



0 ~ 10.00MΩ



Error value



±1%




Clamp sensor measurement range and error (component)















Current measurement range (AC)



Error value



0.000mA ~ 50.00A



±0.2%



 




Product Features:



(1) Automatic range conversion;



(2) Storage of 2000 test data;



(3) Large screen LCD (320×240 LCD) display, Chinese menu operation prompts;



(4) Realize simultaneous display of waveform and measurement processing data on the same screen, making the test process more intuitive;



(5) With setting, calibration and debugging functions.



 It has small measurement workload, quick and simple operation, stable performance, accurate measurement, and high fault detection rate; it can also measure the inductance of reactors, discharge resistance measurement function, live measurement of coupling capacitor current and capacitance, calculate the capacity of the measured capacitance; synchronously display voltage and current waveforms and phase; automatic range conversion, data storage; large screen LCD display, Chinese output, and with printing.



Working Principle:



Due to the use of standard capacitor and tested capacitor synchronous sampling technology, it is not affected by power supply voltage fluctuations; in addition, the measurement process is fully automatic, avoiding errors caused by manual operation, so it has the characteristics of good stability, good repeatability, accuracy and reliability.