Testing Principle
The high-voltage switch mechanical characteristic tester adopts the four-terminal connection method for loop resistance testing. In fact, it tests the dynamic resistance during the switching action, which can be used to test SF6 high-voltage circuit breakers with graphite contacts. The working principle of the dynamic resistance test channel is to load a 10A constant current source on the two terminals of the circuit breaker's graphite contacts. Through the other two test signal lines (voltage signals) connected to both ends of the circuit breaker, it tests the dynamic voltage change waveform within 200mV during the action of the graphite contacts, thereby determining the position of the metal contacts of the circuit breaker, and then inferring the true and exact position of the graphite contacts based on the length of the graphite contacts.
Purpose
This instrument is suitable for mechanical characteristic testing of high-voltage switches such as low-oil, multi-oil, vacuum, and sulfur hexafluoride (SF6) types from both domestic and imported manufacturers. It is also suitable for time testing of electromagnetic action electrical appliances (such as contactors, relays, etc.), and comes with an operating power supply.
Characteristics of the Tester
With the development of society, people have increasingly higher requirements for the safety and reliability of electricity use. Wuhan Zhongshi, high-voltage circuit breakers play the dual role of control and protection in the power system, and their performance directly affects the safe operation of the power system. Mechanical characteristic parameters are one of the important parameters for judging the performance of circuit breakers. High-voltage switch mechanical characteristic tester is designed based on the latest "High-Voltage AC Circuit Breakers" GB1984-2003, and can accurately measure the mechanical dynamic characteristic parameters of various voltage levels of low-oil, multi-oil, vacuum, and sulfur hexafluoride high-voltage circuit breakers.
Technical Parameters
Environmental group: Belongs to Group III instruments in GB6587.1-1986 "General Outline of Environmental Testing for Electronic Measuring Instruments".
1. Time measurement: 12 channels
Inherent opening (closing) time
Phase-to-phase difference within opening (closing)
Phase-to-phase difference between opening (closing) and closing (opening) bounce time (bounce count)
Test range: 0.1ms ~ 999.99ms
Accuracy: 0.5%±(1% reading + 2 digits)
2. Speed measurement: Just-open (just-close) speed
Average speed over specified time period (stroke segment or angle segment)
Maximum opening (closing) speed
Speed measurement range: 1mm sensor 0.01 ~ 25.00m/s,
0.1mm sensor 0.001 ~ 2.50m/s,
0.5° angle sensor 1 cycle / 0.5°
Accuracy: 1mm sensor ±(1% reading + 1 digit)
0.1mm sensor ±(2% reading + 1 digit)
0.5° angle sensor ±(1% reading + 1 digit)
3. Stroke measurement: Moving contact stroke (stroke)
Contact stroke (opening distance)
Overshoot stroke
Rebound stroke (amplitude)
Sensor: 50mm, resolution: 0.1mm
Sensor: 300mm (optional), resolution: 1mm
Angular velocity B1 sensor: 360°, resolution: 0.5 °, accuracy: ±1%
4. Display: 320×240 LCD screen, contrast adjustable
5. Data storage: Can store 100 sets of measurement data
6. Printer: High-speed thermal printer
7. AC power: AC 220V ± 10%; 50Hz ± 2%
8. DC power: Output voltage: 30 ~ 260V continuously adjustable, output current: ≤15A (short time)
9. Main unit volume: 380×280×140mm
10. Operating environment: -10℃~+50℃
11. Relative humidity: ≤90%