AC/DC High Current Generator (Current Transformer Ratio and Polarity Tester)
AC/DC High Current Generator (Current Transformer Ratio and Polarity Tester) is specifically designed for testing the ratio and polarity of current transformers. It integrates a high current generator, primary and secondary digital ammeters, and polarity detection circuits. The product features a reasonable design and is easy to operate.
Technical Specifications:
1. Output current: 0~500A, power: 6kVA.
2. Primary ammeter measurement: 0~1000A, resolution: 0.1A,
Error: ±(0.5% of reading + 2 digits).
3. Secondary ammeter measurement: 0~5A, resolution: 1mA,
Error: ±(0.5% of reading + 2 digits).
4. Power supply voltage: AC220V±10%.
5. Operating environment: temperature 0~+40°C
Humidity less than 85% without condensation
6. Dimensions: 360mm*290mm*280mm
7. Instrument weight: 37kg
(Current Transformer Ratio and Polarity Tester) Accessories:
Specific advantages in work:
1. The AC/DC High Current Generator adopts advanced technology and manufacturing processes, pioneering the application of the latest PWM high-frequency pulse width modulation technology and pulse train logic array modulation. It uses high-power IGBT devices and high-frequency technology to increase the frequency up to 100kHz, resulting in higher output voltage stability and lower ripple coefficient.
2. Smaller size, lighter weight, more aesthetically pleasing, more reliable, easy to operate, and fully functional, making it suitable for field use. It is the most ideal reliable product in the new century.
3. Combines hardware and software anti-interference technologies, ensuring stable performance, strong anti-interference capability, and adaptability to harsh electromagnetic environments.
4. Equipped with grounding detection and zero-return detection functions. Tests can only be conducted after grounding and zero-return are confirmed, ensuring safety and reliability.
5. High voltage regulation stability, smooth voltage adjustment across the full range. The output voltage adjustment uses an imported single multi-turn potentiometer, ensuring smooth voltage boosting and high adjustment precision. It also features coarse and fine adjustment functions. Voltage adjustment accuracy is better than 0.1%, voltage and current measurement error is less than 1.0%, and ripple factor is better than 0.5%.
6. High precision and accurate measurement. Both voltage and current meters are digital displays, with voltage resolution of 0.1kV and current resolution of 0.1uA. The voltmeter on the control box directly displays the voltage applied to the load test object, eliminating the need for an external voltage divider and simplifying wiring. The instrument measures leakage current at both high and low voltage ends. The high voltage end uses a circular shielded digital display, which is resistant to discharge shocks and has good anti-interference performance, suitable for on-site use.
7. Added a high-precision 75% VDC-1mA function, bringing great convenience to zinc oxide arrester testing. A simple press is all it takes, no calculation needed. The control box has a 75% voltage function key. During arrester tests, when the current rises to 1000uA, press the 0.75 button. The values displayed on the voltmeter and ammeter are the 75% data. After completion, immediately return the boost knob to zero, and also return the fine voltage adjustment knob to zero. Then press the green button to cut off high voltage and turn off the power switch. Proceed with other tests.
8. The bottom is equipped with three built-in support legs, increasing the stability of the voltage doubling cylinder.
9. The voltage doubling cylinder has a segmented structure, making it flexible and convenient for field use. One machine can serve multiple purposes, offering economic benefits.
10. Convenient overvoltage setting function, using digital setting. Simply press the setting key and the set key simultaneously to display the set voltage value intuitively, making operation more flexible. The displayed value unit is kV. This machine also has time display and setting functions, as well as a forced start function for the generator power supply.
11. Approaching current boosting algorithm, automatically timing the current endurance after reaching the set target output current, and the motor automatically returns to zero after timing ends.
11. Negative polarity output, zero start, continuously adjustable, with various protection functions such as overvoltage, overcurrent, zero return, grounding protection, and unique disconnection protection. The automatic protection circuit is powerful, providing comprehensive and reliable protection, ensuring safe operation. All technical indicators are superior to industry standards and similar products.