Measuring the DC resistance of transformer windings is a very important test item. In the "Regulations for Power Equipment Testing," it is ranked second among transformer test items. The "Regulations" stipulate that during transformer handover, major repair, minor repair, tap changer position changes, fault inspection, and preventive tests, the DC resistance of transformer windings must be measured. The purposes are:

  To check the welding quality of internal conductors and leads of the windings;

  To check whether the contacts at each position of the tap changer are in good condition;

  To check whether there are any broken points in the windings or leads;

  To check the correctness of parallel branches, and whether there are one or more broken circuits in windings made of several parallel conductors;

  To check for short circuits between layers and turns.

  II. GWZRC-3A DC Resistance Tester Product Features:

  1. Microcomputer-controlled intelligent instrument, capable of storing test results;

  2. AC/DC power supply, portable design, easy to use and carry;

  3. Advanced constant current power technology greatly reduces the instrument's size, weight, and power consumption, further shortening measurement time and ensuring more stable and reliable measurement data.

  4. Large-screen LCD display with blue backlight, suitable for all-weather use;

  5. Built-in micro printer for direct output of print results;

  6. Built-in high-volume buzzer with audible prompt function.

  7. Large-capacity battery, three-stage charging circuit, screen displays battery level, automatic shutdown at low voltage to prevent over-discharge;

  8. This instrument is suitable for measurement and analysis of inductive, low-resistance values such as various power transformer and mutual inductor windings.

  III. GWZRC-3A DC Resistance Tester Technical Parameters:

  Range and Test Current 0~20mΩ--3A

  0~200mΩ--3A

  0~2Ω--3A

  0~20Ω--0.3A

  0~200Ω--0.03A

  0~2kΩ--0.003A

  Accuracy 0.2%±2 digits (25±2℃)

  Dimensions 360 (L)×260 (W)×140 (H) mm

  Weight Approx. 6kg

  Power Supply AC220V±10% Frequency: 50Hz±5%

  Operating Environment Temperature: 0~40℃

  Relative Humidity: ≤80%

  Safety Performance Insulation Resistance: ≥2MΩ

  Leakage Current: ≤5mA