Intelligent Lightning Protection Component Tester
An instrument suitable for testing the DC parameters of overvoltage protection components such as zinc oxide arresters (zinc oxide valve plates and varistors). It has functions such as memory, calculation, hold, self-check, and leakage alarm. It features high-voltage short-circuit protection, overcurrent protection, and high-voltage presetting. The high-voltage self-discharge time is less than 5 seconds.
Functional Features:
1.Suitable for measuring the DC parameters of zinc oxide arresters (varistors), metal-ceramic two-electrode and three-electrode discharge tubes, vacuum lightning arresters, and other overvoltage protection components. It can also be used as a stabilized voltage or constant current power supply for other applications.
2、Equipped with high-voltage short-circuit protection, overcurrent protection, high-voltage presetting, and range adjustment functions. The high-voltage self-discharge time is less than 0.5 seconds.
3、FC-2G Lightning Protection Component Tester / Manufacturer Supply has a self-check function.
4、Measurement data is displayed on a three-and-a-half-digit LCD with high accuracy and good reliability.
5、During measurement, the range can be preset, and an audible alarm is issued for over-range tests, making it suitable for component grouping and inspection.
6、Selecting continuous measurement allows for uninterrupted testing of batch samples.
7、The panel is simple and easy to operate.
8、Lightweight and portable.
Measurement Method:
(a) Connect the varistor under test to the measurement leads, press the "High Voltage On/Off" key, the high-voltage indicator lights up, and the display immediately shows the starting action voltage U1mA test value, followed by the unit "V". Press the "Test" key, and after about 2 seconds, it automatically switches to the leakage current I0.75U1mA test value, with the unit "μA" displayed. The green indicator light synchronously lights up with the leakage current display and disappears after about 2 seconds.
(b) If the U1mA value of the varistor under test is lower than the preset voltage value, the displayed voltage preset value will drop to near its U1mA value after connection. You can press the "Test" key to continue the next step. If it exceeds the upper range limit, the display will show the preset upper range limit during the U1mA test period. At this time, the test current is <1mA, and the displayed test data is invalid. The instrument will emit a buzzer alarm during the I0.75U1mA test (red light on) period. To replace the sample or measure again, simply press the "Test" key again.
(c) For continuous measurement, set the "Single/Continuous" switch to the low position (continuous). (If selecting continuous measurement before turning on the high voltage, press the "Test" key once.)
![]()