Loop Resistance Tester with Printer (150A) Parameters Technical Parameters:
1. Capacitance range: 0.2μF~2,000μF;
Capacity range: 5~20,000 kvar;
Measurement accuracy: ±1.5%×reading ±2 digits;
Resolution: ±1.0%rdg;
2. Inductance range: 1mH~9.99H; Measurement accuracy: ±1.5%±2 digits
3. Output measurement voltage: AC 26V/500VA; 50Hz;
4. Display mode: Large screen LCD with full Chinese output, TPμp-40 panel thermal printer
5. Dimensions and weight: 370×370×220 mm / 8 kg
6. Working conditions:
Ambient temperature: 0℃ ~ +40℃, Relative humidity: ≤90%
Power supply: AC 220V±10%; 50Hz;
Loop Resistance Tester with Printer (150A) Parameter Panel Structure

Operating Instructions
1. According to the four-wire measurement method, connect the test object to the instrument panel using the dedicated test leads. Note that the voltage measurement leads should be connected inside the current output leads.
2. Connect the AC220V power supply (note: the third wire of the power input, i.e., the protective ground, must be connected to the earth), press the power switch. At this time, the ammeter and resistance meter display "000" (one digit may be allowed to fluctuate before the value is set).
3. Press the measurement switch, adjust the current output knob (clockwise) until the ammeter displays "100.0", then read the value on the resistance meter, which is the resistance of the test object, and record it. (If "1" is displayed, it indicates that the measured circuit is over-range).
4. After testing, adjust the current output adjustment knob (counterclockwise) to the minimum, reset the measurement switch, and then turn off the power switch.
5. To repeat the test, simply reset the measurement switch, re-clamp the test clamps, and press the measurement switch again.
Instrument Features
1. LCD display, high-speed thermal printer.
2. This instrument has the characteristics of small size, light weight, strong anti-interference ability, high accuracy, easy operation, and complete protection functions.
3. Human-machine dialogue with full keyboard operation, intelligent working process throughout.
4. It uses precision instrumentation operational amplifiers and high-precision quadruple integral A/D converter, combined with a high-performance 16-bit microcontroller. During measurement, the system automatically switches the amplification factor according to the signal level, ensuring the accuracy of the product's testing.
5. This product also features a real-time calendar clock, providing time reference for printing and data storage.
6. Data storage and historical data browsing function, can store a large amount of data, and has power-off protection function.
Test Configuration
Main unit 1 unit, accessory box 1 (including)
Product user manual 1 copy, test leads 1 set
Print paper 2 rolls, printer manual 1 copy
Fuse 10A 4 pieces, power cord 1 piece