Triple Frequency High Voltage Generator 

Darui Electric recommends for you:


The Triple Frequency High Voltage Generator is a high voltage generator with an output capacity of 3kVA-150kVA.

Operating Environment




1. Power supply conditions: Three-phase 380V/50Hz

2. Ambient temperature: -15℃ to 40℃

3. Altitude: not exceeding 1000 meters

4. Used for AC induced withstand voltage tests of voltage transformers, motors, and transformers, to assess the insulation strength of the main and secondary windings, and can also be used as a 150Hz power source for short-term operation.

5. Input voltage: AC380V 50Hz

6. Output voltage: 300V-500V (0-5kV available upon request) For voltage >300V, an external step-up device is required.


Usage Instructions




1. Connect the working wires according to the test wiring diagram, ensuring that the triple frequency generator's housing is reliably grounded.

2. Turn on the three-phase voltage regulator power supply and adjust the three-phase voltage regulator clockwise to 380V.

3. Turn on the triple frequency power control box; the control box power indicator light (green) will illuminate. Press the start button, and the working indicator light (red) will illuminate. At this point, the triple frequency generator has produced triple frequency and voltage.

4. Rotate the single-phase voltage regulator handle clockwise to increase the voltage to the rated voltage. If the rated voltage cannot be reached, increase the three-phase voltage regulator voltage until the required voltage for the test object is achieved.

5. Closely monitor the instrument readings and the condition of the test object until the required test time is completed.


Technical Parameters




1. Working power supply: Three-phase AC 380V ±10% 50Hz

2. Rated capacity: 3KVA-30KVA (optional)

3. Output voltage: 50—500V (max 750V), 150Hz; 100—1000V (max 1500V), 150Hz

4. Capacity: 1-1000KVA

5. Waveform: Sine wave, distortion less than 1%

6. Load characteristics: Suitable for resistive, inductive, and capacitive loads

7. Output voltage 250V-1000V 150Hz waveform distortion ≤5%

8. Output capacity: 3kVA, 5kVA, 10kVA, 20kVA, 50kVA



Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.
WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us