Capacitance and Inductance Tester

It mainly solves the following problems:

● On-site measurement of a single capacitor requires disconnecting the connecting wires, which is not only heavy workload but also easy to damage the capacitor.

● The low output voltage of the capacitance meter leads to a low fault detection rate.

● Measuring the inductance of reactors.

This instrument has the characteristics of small measurement workload, fast and simple operation, stable performance, accurate measurement, and high fault detection rate. In addition, its current measurement unit can also be used for measuring electrical equipment such as CVTs and arresters, providing multi-functionality in one instrument.

According to the "Technical Measures for Preventing Capacitor Device Accidents", for high-voltage shunt capacitors, the capacitance of each capacitor in the capacitor bank should be measured regularly. It is recommended to use the measurement method without disconnecting the connecting wires to avoid the leakage of the bushing due to stress caused by disassembling and assembling the connecting wires.

Functional Features


● Automatic range conversion;

● Stores 7168 test data;

● Large screen LCD (320×240 LCD) display, Chinese menu operation prompts;

● Realizes simultaneous display of waveform and measurement processing data on the same screen, making the test process more intuitive;

● Has setting, calibration, and debugging functions.

Technical Parameters


● Capacitance range: 0.2μF~2,000μF;

Capacity range: 5~20,000 kvar;

Measurement accuracy: 0.2μF~2μF ±1% reading ±0.02μF;

2μF~2,000μF ±1% reading ±2 digits;

● Inductance range: 1mH~9.99H; Measurement accuracy: ±1.5% reading ±2 digits

● Output measurement voltage: AC 26V/500VA; 50Hz;

● Display mode: large screen LCD full Chinese output, TPμp-40 panel thermal printer

● Dimensions / Weight: 370×370×220 mm / 16 kg

● Working conditions:

a. Ambient temperature: 0℃ ~ +40℃, relative humidity: ≤90%

b. Power supply: AC 220V±10%; 50Hz;